The chlorination system in power
plant or dosing liquid chemicals is installed to treat the water (scale
inhibition and bio-fouling protection) to use in main cooling water system.
Chlorination system shall be
supplied to provide continuous and intermittent shock chlorine dosing to the
seawater intake to fulfill the need of the chlorine for the whole Power Plantpurposes.
The chlorination system shall
have sufficient capacity to allow intermittent shock dosing of hypochlorite
selection into the intake CW pump which can then be directed into either or the
circulating water systems by appropriate sectional isolation of the CW
discharge header.
It is the intent of this
specification that a proven and reliable system shall be provided. The chemicals
and dosage rate shall be established to control of corrosion, bio fouling and
scale formation efficiently and also maintaining residual chlorine in the
cooling water discharge from the main condensers considering the Environmental
Regulation, plant performance and life, water quality variations, economies of
chemical, etc.
The chlorination system shall consist
of the following dosing systems:
- Sodium Hypochlorite dosing system with dosing pumps
- Valves and piping
- Chlorination dosing package, this package has dosing pumps. A test kit for dosing pump is provided for measuring the bacterial content. For the common drives like the filing pump & the chemical drain pump a receptacle is provided for each of the pumps.
The chlorination system shall be arranged
and designed to provide complete flexibility of operation in terms of solution
strength dosing quantity and treatment timings. The solution shall be injected
into the sumps by injection pump from the chemical dosing tank, however.
The chlorination system should be
equipped with all of the system in a complete set including piping, valves,
pumps, control and instrumentation, equipment and accessories as required for normal
operation. The system shall be including to the following component but not
limited to:
- NaOCl dosing pumps
- Bromine dosing pumps
- Scale Inhibitor dosing pumps
- NaOCI dosing tank
- Bromine dosing tank
- Scale Inhibition dosing tank
- Chemical drain pumps
- Residual Chlorine Analyzer skid comprising of Y-type Strainer, Self Priming Pump, and Residual Chlorine Analyzer
- Chemical agitator equipment (including automatic stirrer) and accessories
- Safety equipment including as follow but not limited to:
- Eye Wash Station and Safety Shower
- Warning Horn
- Breathing apparatus (with mask and Glove)
All components of chlorination system
shall be made with suitable materials and has good corrosion / chemical resistant
for long time operation.