Single element drum level control
is one of methods to control drum or boiler level control. The level control of
water/steam is commonly discussed in one among 3 main methods such as single
element drum level control, two element drum level control and also three element drum level control. The use of one of these methods is dependent on the
certain boiler dimensions (economical) and load changes (design).
Single element drum level control
can be probably the most basic method. In this method drum level is calculated
employing a single measurement tool as well as offers a control transmission to
the feedwater regulator with immediate connection to the existing running drum
level. This method is applied in each feedwater control and ON/OFF methods.
Figure 1: Single Element Drum Level Control (Source: Courtesy of Honeywell) |
The single element drum level control
method is exclusively efficient for small steam boilers having reasonably
constant requirements and also gradual to quite small load alterations. This is
mainly because the impact of swell and shrink which leads to an inappropriate
preliminary control response, that can bring on under filling down or over
filling up of steam drum.
Because steam need grows, there's
a preliminary decreasing of steam drum pressure leading to an unnatural increase
inside drum level since the steam bubbles increase and enlarge the water level
of drum. This happening directs a wrong control transmission to decrease
feedwater flow, if actually the feedwater flow must be greater to manage amount
balance.
On the other hand, on a reduction
of steam need, there's a preliminary increasing of pressure of steam drum that
serves to decrease the drum level through decreasing steam bubbles and also
diminishing the level of drum water. This directs a wrong transmission to maximize
feedwater flow if actually it must be reducing to manage amount balance.
Operations encountering immediate
or significant load alterations, can certainly lead to ‘phasing’ impact of
swell and shrink leading to the controller of water level to get rid of command
of drum level along with cause annoyance small water trips or even excessive
carry-over and also water priming.